dc.identifier.citation | CARVALHO, Enio Nascimento. Modelagem e simulação de unidades resfriadoras de líquidos por absorção H2O-libr de simples e duplo efeito, incluindo o efeito de aditivos e clima local. 2007. 126 f. Dissertação (Mestrado em Ciências Mecânicas)—Departamento de Engenharia Mecânica, Universidade de Brasília, Brasília, 2007. | en |
dc.identifier.uri | http://repositorio.unb.br/handle/10482/1843 | - |
dc.description | Dissertação (mestrado)—Universidade de Brasília, Faculdade de Tecnologia, Departamento de Engenharia Mecânica, 2007. | en |
dc.description.abstract | A finalidade deste trabalho é a modelagem física e simulação numérica de unidades
resfriadoras de Líquidos por absorção a H2O-LiBr, nas configurações a simples e duplo
efeito, com análise do efeito da utilização de aditivos na solução de H2O-LiBr e da
influência do clima local sobre o desempenho e consumo energético da unidade. O
modelamento físico de cada um dos componentes do sistema foi adotado baseando-se nos
princípios clássicos da conservação de energia, junto com as correlações aplicáveis da
transferência de calor e massa e equações que descrevem as propriedades dos fluidos de
trabalho. O modelo adota um conceito semi-empírico, ou seja, parâmetros característicos
para cada componente do sistema são utilizados. A aplicação do modelamento e simulação
é realizada para quatro estudos de caso. No primeiro estudo de caso é simulada a operação
de uma unidade resfriadora de líquido, de simples efeito, para as 8760 horas do ano, com
aplicação em um edifício comercial. A simulação de uma unidade por absorção de duplo
efeito, com estimativa do consumo de gás natural, durante o período de um ano de
operação da máquina, é o objeto do estudo de caso dois. No terceiro estudo de caso, o
consumo anual de combustível e desempenho de uma unidade de resfriamento de duplo
efeito é comparado, para duas localidades climáticas diferentes. Finalmente, a avaliação da
influência do uso de aditivos à solução H2O-LiBr, sobre o desempenho da unidade
resfriadora é analisado no quarto estudo de caso, onde, se obteve um ganho no coeficiente
de performance de até 5,5%, se comparado ao desempenho com uso da solução
convencional de H2O-LiBr. Dessa forma, os resultados obtidos nesse trabalho permitem
uma avaliação sobre a influência de vários fatores, no desempenho de unidades
resfriadoras de líquidos por absorção e por conseqüência em seu consumo energético. _____________________________________________________________ ABSTRACT | en |
dc.description.abstract | The purpose of this work is the physical modeling and simulation of H2O-LiBr absorption
chillers, in the single and double effect settings, with analysis of the effect of the use of
additives in the solution of H2O-LiBr, and the influence of local climate on the
performance and energy consumption of the unit. The physical modeling of each
component of the system was adopted based on the classical principles of the energy
conservation, along with the correlations for the heat and mass transfer or equations that
describe the properties of the fluids of work. The model adopts a semi-empirical approach,
where characteristic parameters for each component of the system are used. The
application of physical modeling and simulation is carried out for four case studies. In the
first case study is simulated the operation of a single effect chiller unit, for 8760 hours of
the year, with implementation in a commercial building. The simulation of a double effect
absorption machine with estimated consumption of natural gas during the period of one
year of operation of the machine is the subject of the second case study. In case study
three, the annual consumption of fuel and performance of a double effect absorption
machine is compared for two different climatic areas. Finally, the evaluation of the
influence of the use of additives to the solution H2O-LiBr, on the performance of the
absorption chiller is analyzed in the fourth case study, where, was obtained an
improvement in the COP of the system up to 5.5%, when compared with the COP of the
conventional solution of H2O-LiBr. Thus, the results obtained in this work provide an
assessment on the influence of various factors in the absorption chiller performance and
result in their energy consumption. | en |
dc.language.iso | Português | en |
dc.rights | Acesso Aberto | en |
dc.title | Modelagem e simulação de unidades resfriadoras de líquidos por absorção H2O-LiBr de simples e duplo efeito, incluindo o efeito de aditivos e clima local | en |
dc.title.alternative | Modeling and simulation of single and double effect H2O-LiBr absorption chillers , including the effect of additives and local climate | en |
dc.type | Dissertação | en |
dc.subject.keyword | Refrigeração por absorção | en |
dc.subject.keyword | Ciclo de refrigeração | en |
dc.subject.keyword | H2O-LiBr | en |
dc.subject.keyword | Simulação (Computadores) | en |
dc.location.country | BRA | en |
dc.description.unidade | Faculdade de Tecnologia (FT) | pt_BR |
dc.description.unidade | Departamento de Engenharia Mecânica (FT ENM) | pt_BR |
dc.description.ppg | Programa de Pós-Graduação em Ciências Mecânicas | pt_BR |
Aparece nas coleções: | Teses, dissertações e produtos pós-doutorado
|