Skip navigation
Please use this identifier to cite or link to this item: http://repositorio.unb.br/handle/10482/36960
Files in This Item:
File Description SizeFormat 
2019_LarissaMarquesPeres.pdf3,2 MBAdobe PDFView/Open
Title: Proteção diferencial de transformadores de potência baseada na corrente de sequência negativa
Authors: Peres, Larissa Marques
Orientador(es):: Silva, Kleber Melo e
Assunto:: Proteção diferencial
Transformadores de potência
Inteligência artificial
Corrente de sequência negativa
Issue Date: 19-Feb-2020
Citation: PERES, Larissa Marques. Proteção diferencial de transformadores de potência baseada na corrente de sequência negativa. 2019. xiv, 110 f., il. Tese (Doutorado em Engenharia Elétrica)—Universidade de Brasília, Brasília, 2019.
Abstract: Propõe-se na presente tese um novo algoritmo de proteção diferencial para transformadores de potência baseado na corrente de sequência negativa, a qual é reconstruída no tempo a partir do fasor correspondente em ambos os enrolamentos do transformador. Com o objetivo de fornecer uma operação mais rápida e confiável do método proposto, a relação dos sinais de corrente de sequência negativa de operação e restrição é integrada. O algoritmo desenvolvido ainda incorpora uma função que detecta a ocorrência de distúrbios, e uma nova estratégia de restrição harmônica também é proposta, para melhorar a segurança da proteção para faltas externas que levem à saturação do transformador de corrente (TC). A fim de avaliar o desempenho do algoritmo proposto, diversos distúrbios são simulados no software Alternative Transients Program (ATP), a saber: curtos-circuitos externos, saturação do TC, remoção de um curto-circuito próximo ao transformador, condição de energização solidária e faltas internas, variando o tipo de curto-circuito, porcentagem de espiras curto-circuitadas, força das fontes e o carregamento do sistema de potência. Além disso, realizou-se uma avaliação comparativa da proteção diferencial proposta com a proteção diferencial tradicional de corrente (fundamentada nos elementos de fase e sequência negativa). Por fim, a lógica do algoritmo proposto foi implementada em um relé de proteção diferencial comercial, possibilitando a sua validação experimental. Os resultados obtidos revelam que o método desenvolvido é capaz de detectar faltas entre espiras e espira-terra, mesmo para 1% de espiras curto-circuitadas, de forma que pode ser um complemento às funções diferenciais de fase, no que concerne a operações mais rápidas e sensíveis para faltas internas envolvendo poucas espiras, e seguro para curtos-circuitos externos com saturação do TC.
Abstract: The present thesis proposes a new power transformers differential protection algorithm based on the negative sequence current, which is reconstructed in time from the corresponding phasor at both transformer windings. Aiming to provide a faster and more reliable operation of the proposed method, the ratio of the operating and restraint negative sequence current signals is integrated during the time. The proposed method also incorporates a function that detects disturbances nearby the transformer, and a new harmonic restraint strategy is also proposed, to improve protection security for external faults with current transformer (CT) saturation. In order to evaluate the performance of the proposed algorithm, a wide variety of disturbances is simulated in the software Alternative Transients Program (ATP): external short-circuits, CT saturation, transformer nearby external fault removal, sympathetic inrush condition and internal faults, by varying the fault type, short-circuited turns percentage, sources strength and the power system loading. In addition, it was performed comparative evaluation between the proposed differential protection and the current traditional differential protection (based on the phase and negative sequence elements). Finally, the proposed algorithm logic was implemented in a commercial differential protection relay, allowing its experimental validation. The obtained results reveal that the proposed method is able to detect turn-to-turn and turn-to-ground faults, even for 1% of short-circuited turns, so that it can be a complement to the phase differential functions, for a faster and more sensitive operations for internal faults involving few turns, and safe for external short-circuits with CT saturation.
Description: Tese (doutorado)—Universidade de Brasília, Faculdade de Tecnologia, Departamento de Engenharia Elétrica, 2019.
Licença:: A concessão da licença deste item refere-se ao termo de autorização impresso assinado pelo autor com as seguintes condições: Na qualidade de titular dos direitos de autor da publicação, autorizo a Universidade de Brasília e o IBICT a disponibilizar por meio dos sites www.bce.unb.br, www.ibict.br, http://hercules.vtls.com/cgi-bin/ndltd/chameleon?lng=pt&skin=ndltd sem ressarcimento dos direitos autorais, de acordo com a Lei nº 9610/98, o texto integral da obra disponibilizada, conforme permissões assinaladas, para fins de leitura, impressão e/ou download, a título de divulgação da produção científica brasileira, a partir desta data.
Appears in Collections:Teses, dissertações e produtos pós-doutorado

Show full item record " class="statisticsLink btn btn-primary" href="/jspui/handle/10482/36960/statistics">



Items in DSpace are protected by copyright, with all rights reserved, unless otherwise indicated.